DC Line Model: BPA_D
To be documented.
Model Equations and/or Block Diagrams
PDF file to be added, please contact us.
Parameters:
| ControlMode_r | Rectifier Control Mode: 0 = power control; 1 = current control |
| ControlMode_i | Inverter Control Mode: 0 = power control; 1 = current control |
| MSU_r | Rectifier Margin switching unit key. A zero indicates that this situation has a margin switching unit, otherwise a margin swithcing unit is assumed not to exist for this station |
| MSU_i | Inverter Margin switching unit key. A zero indicates that this situation has a margin switching unit, otherwise a margin swithcing unit is assumed not to exist for this station |
| TC_r | Rectifier Current measuring circuit time constant in seconds |
| TC_i | Inverter Current measuring circuit time constant in seconds |
| TV_r | Rectifier Voltage measuring circuit time constant in seconds |
| TV_i | Inverter Voltage measuring circuit time constant in seconds |
| T1_r | Rectifier Current regulator time constant in seconds |
| T1_i | Inverter Current regulator time constant in seconds |
| T2_r | Rectifier Current regulator time constant in seconds |
| T2_i | Inverter Current regulator time constant in seconds |
| T3_r | Rectifier Current regulator time constant in seconds |
| T3_i | Inverter Current regulator time constant in seconds |
| KA_r | Rectifier Current Regulotr gain in per unit DC voltage diviced by per unit DC current |
| KA_i | Inverter Current Regulotr gain in per unit DC voltage diviced by per unit DC current |
| IMAX_r | Rectifier Overload current capability in per unit |
| IMAX_i | Inverter Overload current capability in per unit |
| IMARGIN_r | Rectifier Current margin in per unit |
| IMARGIN_i | Inverter Current margin in per unit |
| ALPHASTOP_r | Rectifier Minimum firing angle in degress for operation of this sation as an inverter. The minimum firing angle for rectifier operation is specified in the power flow data |
| ALPHASTOP_i | Inverter Minimum firing angle in degress for operation of this sation as an inverter. The minimum firing angle for rectifier operation is specified in the power flow data |
| TD_r | Rectifier Commutating voltage time constant in seconds |
| TD_i | Inverter Commutating voltage time constant in seconds |
| VLIM_r | Rectifier percent of rated terminal voltage where current limiting begins |
| VLIM_i | Inverter percent of rated terminal voltage where current limiting begins |